PSV Sizing Calculations: Pressure Safety Valve Design Guide


Typical Scenarios For Design Of PSV

Welcome curious minds!

Imagine a pressure vessel operating normally at 8 barg.

Everything looks fine. The temperature is under control, cooling water is available, control valves are functioning and the process is stable.

Now imagine one of these things happens:

  • A control valve fails fully open.
  • Cooling water is lost.
  • A downstream valve is accidentally closed.
  • A condenser stops working.
  • An external fire heats the vessel.
  • A high-pressure tube ruptures inside a heat exchanger.

The pressure starts rising. The vessel does not know that something has gone wrong—it simply responds to the laws of thermodynamics.

If the pressure exceeds the equipment's allowable limit, the result can be equipment damage, loss of containment, fire, explosion or, in the worst case, loss of life.

This is where the Pressure Safety Valve (PSV) becomes the last line of defence.

A PSV normally sits quietly during plant operation. But when the pressure reaches its set point, it automatically opens and releases fluid to prevent the protected equipment from exceeding its allowable pressure.

In simple terms; a safety valve is not designed to control normal operating pressure. It is designed to protect equipment when something goes wrong.

The real engineering question is, how much fluid must the PSV discharge during the worst credible overpressure scenario, and what orifice size is required to handle that flow?

That is the essence of PSV sizing.

What is Pressure Relief Valve?

Pressure Relief Valve (PRV) is a general term for pressure-operated devices used to protect pressure vessels, piping and process equipment from excessive pressure.

Depending on the service, different types are used.

Safety valve-

Generally used for gas or vapour service. It normally has a rapid or "pop" opening action when the set pressure is reached.

Relief valve-

Generally associated with liquid service and normally opens progressively as pressure increases.

Safety relief valve-

Can be used for either liquid or gas/vapour service, depending on its design and certification.

Thermal relief valve-

A small relief valve generally used to protect blocked-in liquid systems.

For example, liquid trapped between two closed valves can experience a large pressure increase from only a small temperature rise because liquids have very little compressibility.

Why does safety valve opens?

A PSV does not open simply because the process pressure is "high." It opens when the pressure at its inlet reaches its set pressure, according to its operating characteristics. But the more important question for the engineer is; why is the pressure increasing?

Before sizing a PSV, we must identify the credible overpressure scenarios.

Typical scenarios include:

  1. External fire
  2. Cooling-water failure
  3. Control valve failure
  4. Loss of condenser
  5. Reboiler steam valve failure
  6. Blocked outlet
  7. Reverse flow
  8. Heat-exchanger tube rupture
  9. Vessel over fill
  10. Loss of instrument air or electrical power
  11. Runaway exothermic reaction
  12. Thermal expansion of blocked-in liquid

The valve is then sized for the scenario that produces the governing required relief load.

In other words; first determine what can go wrong. Then determine how much fluid must be relieved. Only after that should the PSV be sized.

Relief load-

Suppose a vessel contains a liquid that can boil if enough heat enters the vessel.

During a fire, heat enters the vessel. That heat causes the liquid to vaporize.

The PSV now has to remove the generated vapour fast enough to prevent the pressure from exceeding the allowable limit. This generated vapour is the required relief load.

Therefore, PSV sizing can be thought of as a simple chain:

PSV Sizing Steps

External fire case --

External fire is one of the most important scenarios for vessels containing flammable or vaporizing liquids.

Heat is transferred through the vessel wall and absorbed by the liquid. This heat eventually produces vapour, which becomes the relief load. Heat input is calculated as,

q = 21000 x F x A0.82

Where:

q -heat input

F - environmental factor

A - relevant wetted surface area

For a bare, uninsulated vessel, the environmental factor may be taken as (F=1) under the stated basis.

Once the heat input is known, the corresponding vaporization rate can be estimated from:

W = q/ λ

Where:

W = required relief mass flow

q = heat input

λ = latent heat of vaporization

Cooling-water failure

Consider an exothermic reactor normally cooled by cooling water.

If cooling is lost:

Cooling stops → temperature rises → reaction rate may increase → vapour generation increases → pressure rises.

The PSV must therefore be capable of handling the resulting peak relief load.

Control valve failure

A control valve normally regulates flow.

Suppose a high-pressure steam valve normally operates at 40% opening. If it fails fully open, the maximum available steam flow may enter the equipment.

This can create excessive heat input and vapour generation.

Therefore, a control valve that is normally a regulator can become an overpressure source during a failure scenario.

Loss of condenser

A distillation column normally sends overhead vapour to a condenser.

If condenser cooling is lost, vapour is no longer effectively condensed. Vapour accumulation can increase column pressure.

The relief load may therefore be related to the maximum vapour generation rate.

The simplified relationship given in the source material is:

W = 1.1 × Line Flow

The actual basis must be confirmed against the process design and applicable standard.

Reboiler steam valve failure

If the reboiler steam control valve fails open:

Maximum utility flow → maximum heat input → increased process vaporization → increased relief load.

The source material gives:

W = (Maximum Utility Flow × λutility) / λprocess

An important point is that the heating medium does not directly become the relief load. Its heat energy is converted into equivalent vaporization of the process fluid.

Heat exchanger tube rupture

Consider a heat exchanger where one side operates at 20 barg and the other at 5 barg.

If a high-pressure tube ruptures, high-pressure fluid can suddenly enter the low-pressure side.

This can create a very large inflow and rapidly increase pressure.

The source material uses the following simplified double-ended tube rupture basis:

W = 2 × Flow through tube cross-section

However, applicability of this assumption must be checked against exchanger geometry, failure scenario and the applicable design standard.

Blocked outlet

This is one of the easiest scenarios to understand.A pump continues to discharge liquid, but the downstream valve is accidentally closed.

Where does the liquid go?

If there is no alternative flow path, pressure rises rapidly.

The relief load must be based on the maximum credible flow entering the blocked system.

The simplified source basis is:

W = 1.1 × Line Flow

Actual hydraulic conditions should always be considered.

Reverse flow

Check valves are installed to prevent reverse flow—but they are not an absolute guarantee.

A failed or leaking check valve can allow:

High-pressure system → failed check valve → low-pressure vessel

The low-pressure equipment must therefore be checked for the resulting inflow and pressure rise.

Vessel overfill

Imagine a vessel receiving liquid through a failed-open feed valve while its outlet is blocked.

The liquid level continues to rise.

An overfilled or liquid-filled vessel can create a serious hydraulic pressure scenario, particularly when there is little or no compressible volume available.

Therefore, overfill scenarios must be evaluated based on the actual equipment configuration and available relief path.

Loss of instrument air or electrical power

A utility failure can cause several process changes simultaneously.

For example; some control valves may fail open, others may fail closed, pumps may stop,cooling systems may stop or compressors or fans may trip.

Therefore, loss of instrument air or electrical power should not always be considered as one isolated event.

Runaway exothermic reaction

An exothermic reaction releases heat.

If cooling is lost, temperature can increase. In some reactions, higher temperature increases reaction rate, which produces even more heat.

This can create dangerous positive feedback:

Temperature ↑ → Reaction rate ↑ → Heat generation ↑ → Vaporization ↑ → Pressure ↑

The heat generation rate q is calculated as: q=ΔHrx  x  m

Where:

ΔHrx -Heat of reaction.

m-Mass of reaction.

This heat causes rapid vaporization inside the vessel. The required relief valve venting rate w is determined by, W=q/ λ

Set Pressure, MAWP and Relieving Pressure

Three pressures are commonly confused during PSV design.

Operating pressure- The normal pressure at which the equipment operates.

MAWP-Maximum Allowable Working Pressure (MAWP) is the maximum pressure permitted for the equipment under its design basis.

PSV set pressure-The pressure at which the PSV is set to open according to its specified characteristics. For the basis presented in the source material, the PSV set pressure is generally aligned with the equipment MAWP.

But there is an important distinction; the PSV does not necessarily size using the set pressure alone.

During an actual relief event, pressure can rise above the set pressure within the permitted overpressure or accumulation. Therefore, PSV sizing uses the relieving pressure applicable to the scenario.

What is accumulation?

Suppose; MAWP = 10 barg and PSV Set Pressure ≈ 10 barg

Does this mean the PSV must maintain the vessel exactly at 10 barg?

Not necessarily. During a relief event, pressure may rise above the set pressure within the allowable accumulation specified for the applicable design case.

The source material identifies typical values of:

Normal/single operational case — 10%

Multiple PSV installations — 16%

External fire case — 21%

Steam boilers — 3%

These values must always be verified against the applicable code, standard, equipment category and design case before being used for an actual design.

For the fire case used in the example:

P₁ = Set Pressure + allowable fire overpressure + atmospheric pressure

Backpressure — The pressure waiting at the PSV outlet

A PSV may be correctly sized on the inlet side and still experience a problem if the outlet system creates excessive backpressure. Backpressure is the pressure acting at the PSV outlet during discharge. It can be broadly considered as:

Superimposed backpressure

A PSV may be correctly sized on the inlet side and still have a problem if its outlet system creates excessive backpressure. Backpressure is the pressure acting at the PSV outlet during discharge.

It can be divided into:

Superimposed backpressure

Pressure already present in the discharge system before the PSV opens.

Example: pressure in a common flare header.

Built-up backpressure

Additional pressure generated by friction and pressure losses while the PSV is discharging.

Because the pressure difference available across the valve affects its ability to pass the required flow.

Excessive backpressure can also cause chattering—rapid opening and closing of the valve.

Chattering is undesirable because it can damage the valve and reduce effective relief capacity.

Actual PSV Sizing Calculation

Once the governing relief scenario and required relief load are established, we can determine the required PSV discharge area.

For gas/vapour service under critical-flow conditions, the source material uses the API 520 basis.

Where the parameters are defined as:

A: Required effective discharge orifice area in2.

W: Required mass relief flow rate lb/hr.

T: Absolute relieving temperature (R= F + 460).

Z: Compressibility factor of the real gas at relieving conditions (dimensionless, ideal gas =1).

C: Gas constant coefficient determined by the fluid's specific heat ratio (k = Cp/Cv).

Kd: Effective coefficient of discharge (typically 0.975for certified vapor service valves).

P1: Upstream absolute relieving pressure (psia).

Kb: Backpressure capacity correction factor (equals 1.0 for conventional valves or when backpressure is low).

M: Molecular weight of the relieving gas (lb/lb-mol).

 

Let us apply the above concept to a simple fire case.

Given

Fluid = Hexane

Molecular weight = 86

Tank diameter = 1,500 mm

Liquid height = 1,800 mm

Design pressure = 10 kg/cm²(g)

Relieving temperature = 85°C

Tank = non-insulated

Consider external fire scenario

Let us solve the example,

Wetted surface area of tank (A) = (π D L)+(1.1 x (π/4) x D2) = (π x 1.5 x1.8)+(1.1 x 0.785 x (1.5)2)

                                                   =8.482 + 1.944 = 10.426 m2 = 10.426 /(0.3048)2 = 112.18 ft2

 

Heat absorption rate (q) = 21000 x F x A0.82 = 21000 x 1 x (112.18)0.82 = 1007279.4 Btu/Hr

                                           = 1007279.4 x 0.252 = 253834.4 Kcal/Hr

For bare tank F=1, Reference table attached as below.

Latent heat of vaporization of Hexane (λv) = 80 Kcal/Kg

Relief rate (w) = q/ λv = 253834.4 / 80 = 3172.9 Kg/Hr =3172.9/0.4535 = 6996.5 lb/Hr

For PSV orifice sizing calculation,

Mol.wt M = 86

Compressibility (Z) = 1

Gas flow constant C = 322

Discharge coeff Kd = 0.65

Back pressure correction factor Kb = 0.81 (ref graph attached below)

Absolute temp (T) = (1.8 x 85 +32) +460 = 645 0R

Absolute relieving pressure (P1) is set pressure + 21% fire overpressure accumulation

P1 = (10 + (10 x 21%) ) x 14.5 +14.5 = 189.95 psia

Discharge area is calculated as,

Put all values in above mentioned equation,

Orifice area =0.595 inch2

PSV may look like a relatively small piece of equipment compared with a reactor, column or pressure vessel.

But its job is enormous. Under normal operation, we may never notice it.

During an emergency, however, the PSV may become the most important piece of equipment connected to the vessel. But the underlying concept is surprisingly simple:

A pressure relief valve must be capable of removing the required amount of fluid before the protected equipment exceeds its allowable pressure.

That is the essence of PSV sizing. Happy Reading…….

 