PSV Sizing Calculations: Pressure Safety Valve Design Guide
Imagine a pressure vessel
operating normally at 8 barg.
Everything looks fine. The
temperature is under control, cooling water is available, control valves are
functioning and the process is stable.
Now imagine one of these things
happens:
- A control valve fails fully open.
- Cooling water is lost.
- A downstream valve is accidentally closed.
- A condenser stops working.
- An external fire heats the vessel.
- A high-pressure tube ruptures inside a heat
exchanger.
The pressure starts rising. The
vessel does not know that something has gone wrong—it simply responds to the
laws of thermodynamics.
If the pressure exceeds the
equipment's allowable limit, the result can be equipment damage, loss of
containment, fire, explosion or, in the worst case, loss of life.
This is where the Pressure Safety
Valve (PSV) becomes the last line of defence.
A PSV normally sits quietly
during plant operation. But when the pressure reaches its set point, it
automatically opens and releases fluid to prevent the protected equipment from
exceeding its allowable pressure.
In simple terms; a safety valve
is not designed to control normal operating pressure. It is designed to protect
equipment when something goes wrong.
The real engineering question is,
how much fluid must the PSV discharge during the worst credible overpressure
scenario, and what orifice size is required to handle that flow?
That is the essence of PSV sizing.
What is Pressure Relief Valve?
Pressure Relief Valve (PRV) is a
general term for pressure-operated devices used to protect pressure vessels,
piping and process equipment from excessive pressure.
Depending on the service,
different types are used.
Safety valve-
Generally used for gas or vapour
service. It normally has a rapid or "pop" opening action when the set
pressure is reached.
Relief valve-
Generally associated with liquid
service and normally opens progressively as pressure increases.
Safety relief valve-
Can be used for either liquid or
gas/vapour service, depending on its design and certification.
Thermal relief valve-
A small relief valve generally
used to protect blocked-in liquid systems.
For example, liquid trapped
between two closed valves can experience a large pressure increase from only a
small temperature rise because liquids have very little compressibility.
Why does safety valve opens?
A PSV does not open simply
because the process pressure is "high." It opens when the pressure at
its inlet reaches its set pressure, according to its operating characteristics.
But the more important question for the engineer is; why is the pressure
increasing?
Before sizing a PSV, we must
identify the credible overpressure scenarios.
Typical scenarios include:
- External fire
- Cooling-water failure
- Control valve failure
- Loss of condenser
- Reboiler steam valve failure
- Blocked outlet
- Reverse flow
- Heat-exchanger tube rupture
- Vessel over fill
- Loss of instrument air or electrical power
- Runaway exothermic reaction
- Thermal expansion of blocked-in liquid
The valve is then sized for the
scenario that produces the governing required relief load.
In other words; first determine
what can go wrong. Then determine how much fluid must be relieved. Only after
that should the PSV be sized.
Relief load-
Suppose a vessel contains a
liquid that can boil if enough heat enters the vessel.
During a fire, heat enters the
vessel. That heat causes the liquid to vaporize.
The PSV now has to remove the
generated vapour fast enough to prevent the pressure from exceeding the
allowable limit. This generated vapour is the required relief load.
Therefore, PSV sizing can be
thought of as a simple chain:

External fire case --
External fire is one of the most
important scenarios for vessels containing flammable or vaporizing liquids.
Heat is transferred through the
vessel wall and absorbed by the liquid. This heat eventually produces vapour,
which becomes the relief load. Heat input is calculated as,
q = 21000 x F
x A0.82
Where:
q -heat input
F -
environmental factor
A - relevant
wetted surface area
For a bare, uninsulated vessel,
the environmental factor may be taken as (F=1) under the stated basis.
Once the heat input is known, the
corresponding vaporization rate can be estimated from:
W = q/ λ
Where:
W = required
relief mass flow
q = heat input
λ =
latent heat of vaporization
Cooling-water failure
Consider an exothermic reactor
normally cooled by cooling water.
If cooling is lost:
Cooling stops → temperature rises
→ reaction rate may increase → vapour generation increases → pressure rises.
The PSV must therefore be capable
of handling the resulting peak relief load.
Control valve failure
A control valve normally
regulates flow.
Suppose a high-pressure steam
valve normally operates at 40% opening. If it fails fully open, the maximum
available steam flow may enter the equipment.
This can create excessive heat
input and vapour generation.
Therefore, a control valve that
is normally a regulator can become an overpressure source during a failure
scenario.
Loss of condenser
A distillation column normally
sends overhead vapour to a condenser.
If condenser cooling is lost,
vapour is no longer effectively condensed. Vapour accumulation can increase
column pressure.
The relief load may therefore be
related to the maximum vapour generation rate.
The simplified relationship given
in the source material is:
W = 1.1 × Line Flow
The actual basis must be
confirmed against the process design and applicable standard.
Reboiler steam valve failure
If the reboiler steam control
valve fails open:
Maximum utility flow → maximum
heat input → increased process vaporization → increased relief load.
The source material gives:
W = (Maximum Utility Flow × λutility)
/ λprocess
An important point is that the
heating medium does not directly become the relief load. Its heat energy is
converted into equivalent vaporization of the process fluid.
Heat exchanger tube rupture
Consider a heat exchanger where
one side operates at 20 barg and the other at 5 barg.
If a high-pressure tube ruptures,
high-pressure fluid can suddenly enter the low-pressure side.
This can create a very large
inflow and rapidly increase pressure.
The source material uses the
following simplified double-ended tube rupture basis:
W = 2 × Flow through tube
cross-section
However, applicability of this
assumption must be checked against exchanger geometry, failure scenario and the
applicable design standard.
Blocked outlet
This is one of the easiest
scenarios to understand.A pump continues to discharge liquid, but the
downstream valve is accidentally closed.
Where does the liquid go?
If there is no alternative flow
path, pressure rises rapidly.
The relief load must be based on
the maximum credible flow entering the blocked system.
The simplified source basis is:
W = 1.1 × Line Flow
Actual hydraulic conditions
should always be considered.
Reverse flow
Check valves are installed to
prevent reverse flow—but they are not an absolute guarantee.
A failed or leaking check valve
can allow:
High-pressure system → failed
check valve → low-pressure vessel
The low-pressure equipment must
therefore be checked for the resulting inflow and pressure rise.
Vessel overfill
Imagine a vessel receiving liquid
through a failed-open feed valve while its outlet is blocked.
The liquid level continues to
rise.
An overfilled or liquid-filled
vessel can create a serious hydraulic pressure scenario, particularly when
there is little or no compressible volume available.
Therefore, overfill scenarios
must be evaluated based on the actual equipment configuration and available
relief path.
Loss of instrument air or electrical power
A utility failure can cause
several process changes simultaneously.
For example; some control valves
may fail open, others may fail closed, pumps may stop,cooling systems may stop
or compressors or fans may trip.
Therefore, loss of instrument air
or electrical power should not always be considered as one isolated event.
Runaway exothermic reaction
An exothermic reaction releases
heat.
If cooling is lost, temperature
can increase. In some reactions, higher temperature increases reaction rate,
which produces even more heat.
This can create dangerous
positive feedback:
Temperature ↑ → Reaction rate ↑ →
Heat generation ↑ → Vaporization ↑ → Pressure ↑
The heat generation rate q is
calculated as: q=ΔHrx x m
Where:
ΔHrx -Heat of reaction.
m-Mass of reaction.
This heat causes rapid
vaporization inside the vessel. The required relief valve venting rate w is
determined by, W=q/ λ
Set Pressure, MAWP and
Relieving Pressure
Three pressures are commonly
confused during PSV design.
Operating pressure- The
normal pressure at which the equipment operates.
MAWP-Maximum Allowable
Working Pressure (MAWP) is the maximum pressure permitted for the equipment
under its design basis.
PSV set pressure-The
pressure at which the PSV is set to open according to its specified
characteristics. For the basis presented in the source material, the PSV set
pressure is generally aligned with the equipment MAWP.
But there is an important
distinction; the PSV does not necessarily size using the set pressure alone.
During an actual relief event,
pressure can rise above the set pressure within the permitted overpressure or
accumulation. Therefore, PSV sizing uses the relieving pressure applicable to
the scenario.
What is accumulation?
Suppose; MAWP = 10 barg and PSV
Set Pressure ≈ 10 barg
Does this mean the PSV must
maintain the vessel exactly at 10 barg?
Not necessarily. During a relief
event, pressure may rise above the set pressure within the allowable
accumulation specified for the applicable design case.
The source material identifies
typical values of:
Normal/single operational case —
10%
Multiple PSV installations — 16%
External fire case — 21%
Steam boilers — 3%
These values must always be
verified against the applicable code, standard, equipment category and design
case before being used for an actual design.
For the fire case used in the
example:
P₁ = Set Pressure + allowable
fire overpressure + atmospheric pressure
Backpressure — The pressure waiting
at the PSV outlet
A PSV may be correctly sized on
the inlet side and still experience a problem if the outlet system creates
excessive backpressure. Backpressure is the pressure acting at the PSV outlet
during discharge. It can be broadly considered as:
Superimposed backpressure
A PSV may be correctly sized on
the inlet side and still have a problem if its outlet system creates excessive
backpressure. Backpressure is the pressure acting at the PSV outlet during
discharge.
It can be divided into:
Superimposed backpressure
Pressure already present in the
discharge system before the PSV opens.
Example: pressure in a common
flare header.
Built-up backpressure
Additional pressure generated by
friction and pressure losses while the PSV is discharging.
Because the pressure difference
available across the valve affects its ability to pass the required flow.
Excessive backpressure can also
cause chattering—rapid opening and closing of the valve.
Chattering is undesirable because
it can damage the valve and reduce effective relief capacity.
Actual PSV Sizing Calculation
Once the governing relief
scenario and required relief load are established, we can determine the
required PSV discharge area.
For gas/vapour service under critical-flow conditions, the source material uses the API 520 basis.
Where the parameters are defined as:
A: Required effective discharge
orifice area in2.
W: Required mass relief flow rate
lb/hr.
T: Absolute relieving temperature
(R= F + 460).
Z: Compressibility factor of the
real gas at relieving conditions (dimensionless, ideal gas =1).
C: Gas constant coefficient
determined by the fluid's specific heat ratio (k = Cp/Cv).
Kd: Effective
coefficient of discharge (typically 0.975for certified vapor service valves).
P1: Upstream absolute
relieving pressure (psia).
Kb: Backpressure
capacity correction factor (equals 1.0 for conventional valves or when
backpressure is low).
M: Molecular weight of the
relieving gas (lb/lb-mol).
Let us apply the above concept to
a simple fire case.
Given
Fluid = Hexane
Molecular
weight = 86
Tank diameter
= 1,500 mm
Liquid height
= 1,800 mm
Design
pressure = 10 kg/cm²(g)
Relieving
temperature = 85°C
Tank =
non-insulated
Consider external
fire scenario
Let us solve the example,
Wetted surface area of tank (A) =
(π
D L)+(1.1 x (π/4) x D2) = (π x
1.5 x1.8)+(1.1 x 0.785 x (1.5)2)
=8.482 + 1.944 = 10.426 m2 = 10.426 /(0.3048)2 =
112.18 ft2
Heat absorption rate (q) = 21000
x F x A0.82 = 21000 x 1 x (112.18)0.82 = 1007279.4 Btu/Hr
=
1007279.4 x 0.252 = 253834.4 Kcal/Hr
For bare tank F=1, Reference
table attached as below.
Latent heat of vaporization of
Hexane (λv)
= 80 Kcal/Kg
Relief rate (w) = q/ λv
= 253834.4 / 80 = 3172.9 Kg/Hr =3172.9/0.4535 = 6996.5 lb/Hr
For PSV orifice sizing
calculation,
Mol.wt M = 86
Compressibility (Z) = 1
Gas flow constant C = 322
Discharge coeff Kd =
0.65
Back pressure correction factor
Kb = 0.81 (ref graph attached below)
Absolute temp (T) = (1.8 x 85
+32) +460 = 645 0R
Absolute relieving pressure (P1)
is set pressure + 21% fire overpressure accumulation
P1 = (10 + (10 x 21%) ) x 14.5
+14.5 = 189.95 psia
Discharge area is calculated as,
Put all values in above mentioned
equation,
Orifice area =0.595 inch2
PSV may look like a relatively small piece of equipment
compared with a reactor, column or pressure vessel.
But its job is enormous. Under normal operation, we may
never notice it.
During an emergency, however, the PSV may become the most
important piece of equipment connected to the vessel. But the underlying
concept is surprisingly simple:
A pressure relief valve must be capable of removing the
required amount of fluid before the protected equipment exceeds its allowable
pressure.
That is the essence of PSV sizing. Happy Reading…….